Distinguish kW and kVA
Power factor affects apparent power and current. Use equipment and system information at the relevant duty, rather than one assumed factor for every load.
Factory planning for water bottling projects
Plant buying and operating worksheets
Electrical planning needs a state-based load schedule. Separate motor shaft ratings from electrical input, identify which loads can run together and give the responsible electrical designer the starting and power-quality information.
Answer first
List equipment input loads and operating states, then sum the loads that can operate simultaneously in each credible scenario. Keep kW demand, kWh energy and starting requirements separate. Verify power factor, motor starts, protection and available supply through the project electrical design.

01
A motor’s shaft-output rating is not the same as its electrical input. An installed rating is also not a promise of continuous consumption. Keep the basis attached to each figure.
| Field | What to record |
|---|---|
| Equipment identity | Machine, quantity, revision and supplier document |
| Supply | Voltage, frequency, phase and connection boundary |
| Load basis | Electrical input kW, rated current and relevant operating state |
| Operating behavior | Running, standby, cleaning, heating and automatic restart conditions |
| Starting and power quality | Starting method, supplier current/time data, drives and harmonic information |
| Evidence status | Measured value, supplier guarantee, estimate or unresolved input |
02
Illustrative electrical input loads only: production uses 30 kW for process equipment, 12 kW for packing, 45 kW for air and cooling and 8 kW for building services. A 25 kW sanitation package is assumed to operate after production stops. Actual interlocks and operating needs must support that assumption.
| Scenario | Included input loads | Steady demand |
|---|---|---|
| Production | 30 + 12 + 45 + 8 | 95 kW |
| Sanitation only | 25 + 8 | 33 kW |
| Possible overlap | 30 + 12 + 45 + 8 + 25 | 120 kW |
| Illustrative daily energy | 8 hours × 95 kW + 1 hour × 33 kW | 793 kWh |
03
If production and sanitation can overlap, the lower scenario does not establish maximum demand. Keep the overlap as a separate case until sequencing is confirmed. Likewise, an eight-hour energy total does not determine a transformer or protective-device rating.
Power factor affects apparent power and current. Use equipment and system information at the relevant duty, rather than one assumed factor for every load.
A large start or several automatic restarts can produce conditions not represented by the steady kW sum. Give the designer the permitted sequence and supplier starting data.
Show confirmed future loads and the agreed spare-capacity allowance separately. Repeatedly applying hidden margins at machine, panel and service level obscures the design basis.
04
Qualified electrical personnel should collect measurements using approved safe methods. Compare recorded demand and operating state with the design schedule, including the site’s relevant demand interval and supply limitations.
Confirm incoming supply, distribution, machine terminals, earthing, protection and local-work responsibilities in the engineering documents.
Identify bottle format, throughput, compressor state, cooling, heating and other simultaneous users when recording input power.
Use measured or supported kWh over the production schedule and the actual tariff structure. Avoid treating connected kW multiplied by all calendar hours as normal consumption.
R
The references support the underlying method. The bottling examples and worksheet structures are independently authored planning aids; project requirements determine the final design and acceptance criteria.
Explains motor input power, loading and power factor. The plant-state example on this page uses illustrative inputs.
Buyer questions
The sum is a useful inventory check, but final design also needs simultaneous states, electrical input basis, starting, power quality, protection and local requirements.
No. kW is power; kWh is energy over time. A constant 95 kW load for eight hours uses 760 kWh.
No. It is a load-scheduling example. The responsible electrical designer must determine equipment ratings for the actual installation.
Move this project question forward
An incorrect diversity assumption can oversize the service or cause voltage drop trips and failed starts during real sequences.
Not sure which data matters? Send what you have and state the decision you need to make.
Send electrical supply, water pressure and quality, compressed-air demand, heating or cooling services and drainage limits.
The project desk can identify missing inputs and a practical next step. Final engineering, configuration, compliance and commercial terms remain project-specific.
Allot Tech (Suzhou) Co., Ltd. · sales@allottech.com · Project telephone: +86 186 6213 1120 / +1 818 262 0958